  • 6AV6643-0CD01-1AX1 Siemens SIMATIC MP 277 10″ Touch Multi Panel with retentive memory 10.4″ TFT display 6 MB configuration memory configurable with WinCC flexible 2005 Standard SP1

Specification

General information
Product type designationMP277
Customer-specific   configurationYes


Display
Design   of displayTFT
Screen   diagonal10.4 in
Color   displayYes
Number   of colors65 536
Resolution (pixels)
● Horizontal   image resolution640 Pixel
● Vertical   image resolution480 Pixel
Backlighting
● MTBF   backlighting (at 25 °C)50 000 h


Control   elements
Control   elementsTouch screen
Keyboard fonts
● System   keysNo
● Numeric   keyboardYes
   










Touch operation
● Design   as touch screenYes; analog, resistive
Connection type
● Type   of connection for mouse/keyboard/barcode readerUSB / USB / USB


Installation   type/mounting
Mounting   positionvertical
maximum   permissible angle of inclination without external ventilation35°


Supply   voltage
Type of   supply voltageDC


Processor
Processor   typeARM


Memory
Type of   memoryFlash / RAM
Memory   available for user data6 Mbyte
Capacity   of main memory, max.128 Mbyte


Time   of day
Clock
● TypeHardware clock, battery backup,   synchronizable Yes
● retentiveYes
● synchronizable


Interfaces
Interfaces/bus   type1x RS 422, 1x RS   485, 1x Ethernet (RJ45)
Number   of industrial Ethernet interfaces1
Number   of RS 485 interfaces1
Number   of RS 422 interfaces1
Number   of USB interfaces2; Up to 1 GB
Multimedia   card/SD card slot1x Multimedia Card slot, up to   128 MB


Protocols
Supports   protocol for PROFINET IOYes
PROFIsafeNo
PROFIBUSYes
Protocols (Ethernet)
● TCP/IPYes
Further protocols
● other   bus systemsYes








IP (at   the front)IP65
IP   (rear)IP20
NEMA   (front)NEMA 4x (when installed)






Standards,   approvals, certificates
cULusYes
Suitable   for safety functionsNo
Use in hazardous areas
● ATEX   Zone 22Yes
● FM   Class I Division 2Yes


Ambient   conditions
Ambient temperature during operation
● min.0 °C
● max.50 °C
Ambient temperature during storage/transportation
● min.-20 °C
● max.60 °C
Relative humidity
● Operation,   max.90%


Operating   systems
pre-installed   operating systemWindows CE


Configuration
Message   indicatorYes
Alarm   system (incl. buffer and acknowledgment)Yes
Process   value display (output)Yes
Process   value default (input) possibleYes
Recipe   managementYes
Configuration software
● Configuration   toolWinCC flexible Standard Version   2005 SP1 or higher (to be
ordered   separately)
● STEP   7 Basic (TIA Portal)No
● STEP   7 Professional (TIA Portal)No
● WinCC   flexible CompactNo
● WinCC   flexible StandardYes
● WinCC   flexible AdvancedYes
● WinCC   Basic (TIA Portal)No
● WinCC   Comfort (TIA Portal)Yes
● WinCC   Advanced (TIA Portal)Yes
● WinCC   Professional (TIA Portal)Yes




number   of onlie/runtime                        16






Project languages
● Languages   per project32


Functionality   under WinCC (TIA Portal)
LibrariesYes
Task   plannerYes
Help   systemYes
● Number   of characters per info text80
Message system
● Number   of alarm classes32
● Number   of messages4 000
● Bit   messagesYes
— Number   of bit messages4 000
● Analog   messagesYes
— Number   of analog messages200
● System   messages HMIYes
● System   messages PLCYes
● System   messages, other (SIMATIC S7,Yes
Sinumerik,   Simotion, etc.)
● Lines1
● Number   of characters per message80
● Number   of process values per message8
● Acknowledgment   groupsYes
● Message   indicatorYes
● First/last   valueYes
Recipe management
● Number   of recipes300
● Data   records per recipe500
● Entries   per data record1 000
● Recipe   memory64 KB integrated Flash,   expandable
Variables
● Number   of variables per device2 048
● Number   of variables per screen200
● Number   of variables1 000
● Type   Date & Time2 048
● Limit   valuesYes
● MultiplexingYes
● StructuresYes
Images
● Number   of configurable images500
● Permanent   window/defaultYes


● Start   screen configurableYes Yes
● Image   selection by PLCYes
● Image   number in the PLC
Image objects
● Text   objects10 000 text elements
● Number   of I/O fields per image200
● Number   of date/time fields200
● ReturnYes
● Graphics   objectBit maps, icons, vector graphics
— Icons1 000
Complex image objects
● Status/controlWith SIMATIC S7
● dynamic   objectsDiagrams, bar graphs, sliders,   analog display, invisible buttons
— Number   of objects per project1 000
— Number   of curve diagrams per image10
● MethodsTrend / profile
● Bar   graphs
— Number   of bars per chart10
● Sliders
— Number   of slides per image10
● Pointer   instruments
— Number   of analog indicators per image10
● Limit   value linesYes
● Number   of alphanumerical fields300
—   alphanumeric fields per image200
● Number   of numerical fields2 048
—   numerical fields per image200
● Number   of password fields2 048
● Number   of visible switches per project200
—   visible switches per image200
— hidden   switches per image200
● Number   of status switches per project200
— Number   of status switches per image200
● Number   of selector switches per project200
—   Selector switches per image200
● Number   of decade switches per project200
— Decade   switches per image200
● Number   of signal lamps per project200
—   Signal lamps per image200
Attributes for dynamic objects
● Color   changeYes


● X/Y   movementYes
● HideYes
Lists
● Number   of text lists per project500
● Number   of text lists per image200
● Number   of entries per text list256
● Number   of graphics lists per project400
● Number   of graphic lists per image200
● Number   of entries per graphics list256
Archiving
● Number   of archives per device20
● Number   of measuring points per project20
● Number   of entries per archive10 000
● Message   archiveYes
● Process   value archiveYes
● Archiving   methods
—   Sequential archiveYes
—   Short-term archiveYes
● Memory   locationSD and MultiMediaCard
● Data   storage format
— CSVYes
● Online   evaluation
— using   trend curvesYes
Filters
● cyclicYes Yes
● ToleranceYes
● Change
Security
● Number   of user groups50
● Number   of user rights32
● Password   export/importYes
Logging through printer
● Recording/PrintingAlarms, report (shift report),   color print, hardcopy
Transfer (upload/download)
● Transfer   of configurationMPI/PROFIBUS DP, USB, Ethernet,   automatic transfer recognition
Process coupling
● Connection   to controllerS5, S7-200, S7-300/400, TI 505,   SINUMERIK, SIMOTION, Allen

Bradley (DF1), Allen Bradley   (DF485), Mitsubishi (FX), OMRON

(LINK/Multilink), Modicon   (Modbus) see chapter "System

interfaces"
● S7-1200Yes


Unmatched Customer Service

s03-icon1

After Hours Shipping

s03-icon1

Real Time Order Tracking

s03-icon1

Flexible Delivery Options

s03-icon1

Intact Technical Supports

What Does Our Clients Say

Mitsubishi MR-J4 Servo motor

Laura Navas

Great product, great service and we saved money. Excellent !

2019/12/01

Hongfa Relay enquiry

Daniel Frey

The supplier have a professional team to deal my orders,free technique support,fast shipping,warmly service.They also helped me to built the FANUC and Mitsubishi test bench,good partner,looking forward more cooperation in the future.

2020/01/01

Fanuc servo motor repair from Canada

Clayton Steytler

thanks for you support, your engineers solved my problem, thanks also, and want to send you parts for repair.fast shipping.

2020/02/08

Keyence sensor

EQDR SALES

Original and fast shipping,will order again!good supplier!

2020/02/22

Hongfa Relay&Omron relay

Roly Franco

good quality,well done.works well.

2020/02/28

Board A20B-1002-0710 FANUC

Ollie Santos

Great Seller, item arrive in good order, and work fine, thanks.

2020/04/15

fanuc amplifier A06B-6114/7-H206

Amanda

ship quickly and tested drive well, good supplier

2020/04/18

Elevate Your Business Operations With Hanyu intelligent's Industrial Automation Products

  • Best-in-class sourcing
  • MOQ starts from 1 piece
UP